uP -gb
Transmitter indicator controller for oxidising substances, Mod.uP
Microprocessor based instruments, fully programmable, suitable for panel mounting (IP54 protection degree) and outdoor installation (IP65 housing). Instrument configuration is easily performed via display and keyboard and calibration is automatic.
Measure and temperature are indicated on a 5 digit red LED display.
The electronic unit supplies to the cell the polarization voltage required to make it selective to the specific oxidising substance to be measured.
Mod.uP can be directly connected to the sensor of chlorine, chlorine dioxide, chlorites, ozone, peracetic acid, hydrogen peroxide, bromine, permanganate and to the pertinent temperature sensing element. The measure is compensated for temperature variations, according to dedicated algorithms specific for each parameter, displayed in engineering units and retransmitted on a 4-20 mA or 0-10 V analog output, galvanically isolated, that can be freely associated to any interval inside the measuring range.
The instrument provides 4 digital outputs that can be configured as NC or NO via software and can be programmed as low alarm, high alarm, alarm with hysteresis or windows alarm.
The 4 digital outputs are from relays.
Two digital inputs are available, for digital hold of the measure, and for the connection to an external flowswitch (output freezing in absence of sample flow into the cell).
The instrument is optionally available with cleaning sequence included: in this version it can drive the chemical cleaning of the sensor through a specific algorithm, with programmable timers, driving the detergent pump through R4
relay.
Measuring ranges are:
low concentrations: 0-2000 ppb; 0.00-10.00 ppm. High concentrations: 10.0-2000.0 ppm
The analog output can be freely associated to any interval inside the measuring range.
Power supply: 24 Vdc, 24 Vac, 115 Vac, 230 Vac, ± 10%, 50/60 Hz, max.consumption: 3.3 VA
Some of the typical use of these selective instruments: measure and control of chlorine, chlorine dioxide, chlorites, ozone, peracetic acid, hydrogen peroxide, bromine for the following applications:
dosage of disinfectant in drinking water ,
measure and control of the disinfectant applied in waste water
control of disinfection in the in IV range products preparation
determination of chlorine or other oxidizing substance in sea water
analysis of the oxidizing agent (e.g. peracetic acid, chlorine dioxide, chlorine etc.) in fruit and vegetables disinfection and processing
measure of chlorine in swimming pool water